Steam Pipe Sizing

한국어로 보기

Size a steam line: velocity ranges for low, medium and high pressure steam, how to enter steam as a real gas, and a worked saturated-steam example.

Steam lines are sized on velocity and pressure drop together. Steam is light and compressible, so a modest pipe quickly reaches tens of metres per second and the pressure drop climbs with the square of velocity. Steam mains are normally chosen by pressure-drop allowance; the velocity range then confirms the result.

Typical steam velocity and pressure-drop ranges

Steam serviceVelocity (m/s)Pressure drop (bar / 100 m)
Low pressure (< 2 barg)15–30≤ 0.03
Medium pressure (2–10 barg)15–30use the high-pressure limit
High pressure (> 10 barg)30–60≤ 0.10

Above 8 bar the high-pressure velocity range applies. These are the design guides built into the Line Sizing calculator, drawn from published process design references; the project specification governs.

How to enter steam in the calculator

The calculator treats steam as a gas whose density comes from the real-gas relation:

ρ = P · MW / (Z · R · T)

Worked example — saturated steam main

Saturated steam at 7 barg, 5,000 kg/h, 100 m of commercial steel pipe (roughness 0.045 mm), viscosity 15 µPa·s, Z = 0.94. The allowance is the 0.10 bar per 100 m high-pressure figure as the upper limit; the medium-pressure velocity range is 15–30 m/s.

Inside diameter (mm)Velocity (m/s)Pressure drop (bar / 100 m)Density (kg/m³)
8066.32.014.16
10042.50.6334.16
12527.20.2014.16
15018.90.07884.16

Velocity alone would accept 125 mm (27.2 m/s), but its pressure drop is 0.201 bar per 100 m — twice the allowance. 150 mm gives 18.9 m/s and 0.0788 bar per 100 m and passes both checks. Here the pressure drop, not the velocity, picks the size.

Run your own numbers — pick a pipe size and see velocity and pressure drop instantly. Open the Line Sizing calculator

More guides

Results are for reference and preliminary checks; a qualified engineer must verify them before use. Read the disclaimer